SINAMICS G110M PM240M Power Module FSA 1.5 kW (2 hp)
SINAMICS G110M PM240M Power Module FSB 4 kW (5 hp)
The PM240M Power Modules are suitable for safety-related applications. In conjunction with the CU240M Control Unit, the drive can be transformed into a Safety Integrated drive (see Control Units).
The PM240M Power Modules with integrated line filter class A are suitable for connection to TN and TT supply systems.
Интеграция
PM240M Power Modules feature the following interfaces as standard:
Connection diagram for PM240M Power Module with integrated line filter class A
General technical specifications
|
PM240M Power Modules | |||||
---|---|---|---|---|---|---|
System operating voltage |
380 V (-10 %) ... 480 V (+10 %) 3 AC |
|||||
Grid requirements |
>100 |
|||||
Input frequency |
47 ... 63 Hz |
|||||
Output frequency |
|
|||||
|
0 ... 550 Hz |
|||||
|
0 ... 200 Hz |
|||||
Pulse frequency |
4 kHz (standard); 4 ... 16 Hz (in steps of 2 kHz) see derating data |
|||||
Power factor |
0.95 |
|||||
Inverter efficiency |
95 ... 97 % |
|||||
Output voltage, max. in % of the input voltage |
87% |
|||||
Overload capability |
|
|||||
|
0.37 ... 3 kW (0.5 ... 4 hp): 2 × rated output current for 3 s, 4 kW (5 hp): 1.6 × rated output current for 3 s, |
|||||
Electromagnetic compatibility |
Integrated line filter class A according to EN 55011 |
|||||
Possible braking methods |
Dynamic brake with internal braking resistors (accessories) Dynamic brake with external braking resistors DC brake |
|||||
Line input voltage |
380 V AC |
400 V AC |
440 V AC |
480 V AC |
500 V AC |
|
Resulting brake voltage |
171 V DC |
180 V DC |
198 V DC |
216 V DC |
225 V DC |
|
Disconnection on the DC side permits "fast" braking (max. output current 1 A) |
||||||
Degree of protection 1) |
IP66 (for Control Units, screw-type version) |
|||||
Operating temperature |
-10 ... +55 °C (14 ... +131 °F) |
|||||
Storage temperature |
-40 ... +70 °C (-40 ... +158 °F) |
|||||
Permissible mounting positions |
All |
|||||
Relative humidity |
<95 % RH, condensation not permissible |
|||||
Cooling |
External cooling with motor fan |
|||||
Installation altitude |
Up to 1000 m (3281 ft) above sea level without derating |
|||||
Short Circuit Current Rating |
40 kA |
|||||
Protection functions |
|
|||||
Compliance with standards |
UL, cUL, CE, C-Tick (RCM) |
|||||
CE marking, according to |
EC Low Voltage Directive 73/23/EEC; |
1) Applies to Power Modules and Control Units in the mounted state.
2) Applies to industrial control panel installations to NEC article 409 or UL 508A.
Line voltage |
|
PM240M Power Modules | |||
---|---|---|---|---|---|
|
|
6SL3517-1BE11-3AM0 |
6SL3517-1BE12-3AM0 |
6SL3517-1BE13-3AM0 |
6SL3517-1BE14-3AM0 |
Rated output current Irated1) |
A |
1.3 |
2.2 |
3.1 |
4.1 |
Maximum output currentImax |
A |
2.6 |
4.4 |
6.2 |
8.2 |
Rated power |
kW (hp) |
0.37 (0.5) |
0.75 (1) |
1.1 (1.5) |
1.5 (2) |
Rated pulse frequency |
kHz |
4 |
4 |
4 |
4 |
Efficiency η |
% |
96.8 |
98.1 |
98.2 |
97.3 |
Power loss 2) At rated output current |
kW |
0.025 |
0.032 |
0.041 |
0.052 |
Cooling air requirement |
m3/s (ft3/s) |
0.0048 (0.17) |
0.0048 (0.17) |
0.0048 (0.17) |
0.0048 (0.17) |
Sound pressure level LpA(1 m) |
dB |
– |
– |
– |
– |
Rated input current 3) |
A |
1.3 |
2 |
2.8 |
3.6 |
Line supply connection |
|
|
|
|
|
|
mm2 |
1 ... 2.5 |
1 ... 2.5 |
1 ... 2.5 |
1 ... 2.5 |
PE connection (external connection) |
|
|
|
|
|
|
mm2 |
10 |
10 |
10 |
10 |
Motor connection |
|
|
|
|
|
|
mm2 |
1 ... 2.5 |
1 ... 2.5 |
1 ... 2.5 |
1 ... 2.5 |
Motor cable length, max. Shielded |
m (ft) |
5 (16.41) |
5 (16.41) |
5 (16.41) |
5 (16.41) |
Degree of protection |
|
IP66 |
IP66 |
IP66 |
IP66 |
Dimensions |
|
|
|
|
|
|
mm (in) |
161 (6.34) |
161 (6.34) |
161 (6.34) |
161 (6.34) |
|
mm (in) |
135 (5.31) |
135 (5.31) |
135 (5.31) |
135 (5.31) |
|
mm (in) |
270 (10.63) |
270 (10.63) |
270 (10.63) |
270 (10.63) |
Frame size |
|
FSA |
FSA |
FSA |
FSA |
Weight, approx. |
kg (lb) |
2.1 (4.63) |
2.1 (4.63) |
2.1 (4.63) |
2.1 (4.63) |
1) The rated output current Irated is based on the duty cycle for high overload (HO).
2) Typical values. You can find additional information on the Internet at https://support.industry.siemens.com/cs/document/94059311.
3) The input current depends on the motor load and line impedance. The input currents apply for loading at rated power with a line impedance corresponding to uK = 1 %.
Line voltage |
|
PM240M Power Modules | ||
---|---|---|---|---|
|
|
6SL3517-1BE16-3AM0 |
6SL3517-1BE17-7AM0 |
6SL3517-1BE21-0AM0 |
Rated output currentIrated1) |
A |
5.6 |
7.3 |
8.8 |
Maximum output currentImax |
A |
11.2 |
14.6 |
14.1 |
Rated power |
kW (hp) |
2.2 (3) |
3 (4) |
4 (5) |
Rated pulse frequency |
kHz |
4 |
4 |
4 |
Efficiency η |
% |
97.6 |
97.6 |
97.7 |
Power loss 2) At rated output current |
kW |
0.078 |
0.103 |
0.126 |
Cooling air requirement |
m3/s (ft3/s) |
0.024 (0.85) |
0.024 (0.85) |
0.024 (0.85) |
Sound pressure level LpA(1 m) |
dB |
– |
– |
– |
Rated input current 3) |
A |
5.3 |
6.9 |
8 |
Line supply connection |
|
|
|
|
|
mm2 |
1 ... 2.5 |
1 ... 2.5 |
1 ... 2.5 |
PE connection (external connection) |
|
|
|
|
|
mm2 |
10 |
10 |
10 |
Motor connection |
|
|
|
|
|
mm2 |
1 ... 2.5 |
1 ... 2.5 |
1 ... 2.5 |
Motor cable length, max. Shielded |
m (ft) |
5 (16.41) |
5 (16.41) |
5 (16.41) |
Degree of protection |
|
IP66 |
IP66 |
IP66 |
Dimensions |
|
|
|
|
|
mm (in) |
181 (7.13) |
181 (7.13) |
181 (7.13) |
|
mm (in) |
135 (5.31) |
135 (5.31) |
135 (5.31) |
|
mm (in) |
309 (12.17) |
309 (12.17) |
309 (12.17) |
Frame size |
|
FSB |
FSB |
FSB |
Weight, approx. |
kg (lb) |
3.4 (7.50) |
3.4 (7.50) |
3.4 (7.50) |
1) The rated output current Irated is based on the duty cycle for high overload (HO).
2) Typical values. You can find additional information on the Internet at https://support.industry.siemens.com/cs/document/94059311.
3) The input current depends on the motor load and line impedance. The input currents apply for loading at rated power with a line impedance corresponding to uK = 1 %.
Характеристика
Derating data
Rated power at 400 V 3 AC |
Rated output current in A for a pulse frequency of | |||||||
---|---|---|---|---|---|---|---|---|
kW |
hp |
4 kHz |
6 kHz |
8 kHz |
10 kHz |
12 kHz |
14 kHz |
16 kHz |
0.37 |
0.5 |
1.3 |
1.3 |
1.11 |
0.91 |
0.78 |
0.65 |
0.59 |
0.75 |
1 |
2.2 |
1.9 |
1.5 |
1.3 |
1.1 |
1 |
0.9 |
1.1 |
1.5 |
3.1 |
2.6 |
2.2 |
1.9 |
1.6 |
1.4 |
1.2 |
1.5 |
2 |
4.1 |
3.5 |
2.9 |
2.5 |
2.1 |
1.8 |
1.6 |
2.2 |
3 |
5.6 |
4.8 |
3.9 |
3.4 |
2.8 |
2.5 |
2.2 |
3 |
4 |
7.3 |
6.2 |
5.1 |
4.4 |
3.7 |
3.3 |
2.9 |
4 |
5 |
8.8 |
7.5 |
6.2 |
5.3 |
4.4 |
4 |
3.5 |
1) The permissible motor cable length also depends on the cable type and the selected pulse frequency.
Ambient temperature
Permissible output current as a function of ambient temperature for PM240M Power Modules, frame sizes FSA and FSB
Note:
The operating temperature ranges of the Control Units must be taken into account. The temperature ranges are specified in the technical specifications under Control Units.
Installation altitude
Permissible output current as a function of installation altitude for PM240M Power Modules, frame sizes FSA and FSB
Permissible input voltage as a function of installation altitude for PM240M Power Modules, frame sizes FSA and FSB
Motor frequency
Permissible output current as a function of motor frequency for PM240M Power Modules, frame sizes FSA and FSB
Чертеж
Dimensions of PM240M Power Modules (including CU240M Control Unit)
Изделие: 6SL3517-1BE12-3AM0
SINAMICS G110M POWER MODULE PM240M WITH BUILT IN CL. A FILTER PROTECTION IP65 3AC380-480V +10/-10% 47-63HZ OUTPUT HIGH OVERLOAD: 0,75КВТ FOR 200% 3S,150% 57S,100% 240S SD/MMC-INTERFACE AMBIENT TEMP -10 TO +55 DEG C 135 X 161 X 270 (HXWXD), FSA WITHOUT CONTROL UNIT
Изделие: 6SL3517-1BE13-3AM0
SINAMICS G110M POWER MODULE PM240M WITH BUILT IN CL. A FILTER PROTECTION IP65 3AC380-480V +10/-10% 47-63HZ OUTPUT HIGH OVERLOAD: 1,1КВТ FOR 200% 3S,150% 57S,100% 240S SD/MMC-INTERFACE AMBIENT TEMP -10 TO +55 DEG C 135 X 161 X 270 (HXWXD), FSA WITHOUT CONTROL UNIT