Процеcсор коммуникационный - CP 343S, Ethernet - интерфейс, установка на SPEED-bus шину
Наименование
|
CP 343S TCP/IP |
Тип
|
343-1EX71 |
Описание
|
Используется в системах VIPA 300S, для подключения |
Габаритные размеры, В х Ш х Г, мм
|
40 mm x 125 mm x 120 mm |
Сайт производителя
|
www.vipa.de |
Температура окружающей среды
|
0 °C .. 60 °C |
Серия
|
300S |
Тип интерфейса (электрический)
|
RJ45 |
Модуль CP | Описание | Интерфейс RJ45 | Описание | ||
![]() |
|
![]() |
|
Индикация состояния CP
PW |
RUN green |
STOP |
SF |
L/A |
S |
Meaning |
○ | ○ | ○ | ○ | ○ | ○ |
CP is not power supplied, or there may be a defect. |
● | ● | ○ | ● | X | X |
Start-up (Communication via SPEED-Bus) |
● | ● | ○ | ○ | X | X |
The CP is in RUN with a loaded project. The communication by configured connections is enabled. |
● | ○ | ● | ○ | X | X |
CP is in STOP, the communication by configured connections is disabled or CP has no project and |
● | X | X | X | ● | X |
CP is physically connected to Ethernet. |
● | X | X | X | ☼ | X |
Shows communication via Ethernet (activity) |
● | X | X | X | ○ | ○ |
There is no physically connection to Ethernet. |
● | X | X | X | X | ● |
Speed: 100MBit |
● | X | X | X | X | ○ |
Speed: 10MBit |
on: ● off: ○ flashing: ☼ irrelevant: X
Order no. |
343-1EX71 |
Type | CP 343S TCP/IP, Ethernet-CP 343 SPEED-Bus |
General information |
|
Note | - |
Features | Ethernet CP 343S-NET, SPEED-Bus RJ45 16 connections via Siemens NetPro 64 connections via user program 32 PG/OP connections |
SPEED-Bus | ![]() |
Current consumption/power loss |
|
Current consumption from backplane bus | 550 mA |
Power loss | 2.75 W |
Status information, alarms, diagnostics |
|
Status display | yes |
Interrupts | no |
Process alarm | no |
Diagnostic interrupt | no |
Diagnostic functions | no |
Diagnostics information read-out | possible |
Supply voltage display | green LED |
Group error display | red SF LED |
Channel error display | none |
Ethernet communication CP |
|
Number of productive connections, max. | 64 |
Number of productive connections by Siemens NetPro, max. | 16 |
S7 connections | USEND, URCV, BSEND, BRCV, GET, PUT, Connection of active and passive data handling |
User data per S7 connection, max. | 32 KB |
TCP-connections | SEND, RECEIVE, FETCH PASSIV, WRITE PASSIV, Connection of active and passive data handling |
User data per TCP connection, max. | 64 KB |
ISO-connections | SEND, RECEIVE, FETCH PASSIV, WRITE PASSIV, Connection of active and passive data handling |
User data per ISO connection, max. | 8 KB |
ISO on TCP connections (RFC 1006) | SEND, RECEIVE, FETCH PASSIV, WRITE PASSIV, Connection of active and passive data handling |
User data per ISO on TCP connection, max. | 32 KB |
UDP-connections | SEND and RECEIVE |
User data per UDP connection, max. | 2 KB |
UDP-multicast-connections | SEND and RECEIVE (max. 16 Multicast groups) |
UDP-broadcast-connections | SEND |
Functionality RJ45 interfaces |
|
Type | X1 |
Type of interface | Ethernet 10/100 MBit |
Connector | RJ45 |
Electrically isolated | ![]() |
PG/OP channel | ![]() |
Number of connections, max. | 32 |
Productive connections | ![]() |
Housing |
|
Material | PPE |
Mounting | DIN rail SPEED-Bus |
Mechanical data |
|
Dimensions (WxHxD) | 40 mm x 125 mm x 120 mm |
Weight | 210 g |
Environmental conditions |
|
Operating temperature | 0 °C to 60 °C |
Storage temperature | -25 °C to 70 °C |
Certifications |
|
UL508 certification | yes |
Order no. | Name/Description | |
---|---|---|
341-1AH01 |
CP 341 - Communication processor␍ RS232, isolated Function compatibility to Siemens CP 341 Parameterization via the Siemens parameterization package Data transfer rate up to 76.8 kbit/s Power supply via backplane bus |
![]() ![]() |
341-1CH01 |
CP 341 - Communication processor␍ RS422/485, isolated Function compatibility to Siemens CP 341 Parameterization via the Siemens parameterization package Data transfer rate up to 76.8 kbit/s Power supply via backplane bus |
![]() ![]() |
341-2CH71 |
CP 341S - Communication processor - SPEED-Bus␍ 2x RS422/485, isolated SPEED-Bus Data transfer rate up to 115.2 kbit/s Integrated diagnostics buffer |
![]() ![]() |
342-1CA70 |
CP 342S CAN - CANopen master - SPEED-Bus␍ CANopen master, SPEED-Bus 125 CAN slaves connectable 40 Transmit PDOs, 40 Receive PDOs 1 SDO (Server), 127 SDO (Client) Project engineering: VIPA WinCoCT |
![]() ![]() |
342-1DA70 |
CP 342S DP - PROFIBUS-DP master - SPEED-Bus␍ PROFIBUS-DP master (Class 1), SPEED-Bus RS485 124 DP slaves connectable Project engineering: Siemens SIMATIC Manager Diagnostic facilities |
![]() ![]() |
342-1IA70 |
CP 342S IBS - INTERBUS master - SPEED-Bus␍ INTERBUS master, SPEED-Bus RS422 Diagnostics via LEDs, RS232, Mini-DIN, Dual Port Master Up to 512 slaves connectable |
![]() ![]() |
342-2IA71 |
CP 342S IBS - INTERBUS master - SPEED-Bus␍ Dual INTERBUS master, SPEED-Bus 2x RS422 Diagnostics via LEDs, diagnostics device (2x RJ45), Dual Port Master Up to 512 slaves connectable |
![]() ![]() |
343-1EX71 |
CP 343S TCP/IP - Ethernet-CP 343 - SPEED-Bus␍ Ethernet CP 343S-NET, SPEED-Bus RJ45 16 connections via Siemens NetPro 64 connections via user program 32 PG/OP connections |
![]() ![]() |
343-2AH10 |
CP 343-2P ASI - AS-i master Up to 62 slaves connectable Corresponding to AS-i specification 3.0 (master profile M3) Support of analog slaves concerning profile 7.3 resp. 7.4 Automatic address programming possible (address 0) |
![]() ![]() |
|
Изделие: 342-1DA70
Для шины SPEED-Bus, ведущее устройство сети PROFIBUS DP (RS-485, 12 Мбод, Class 1), поддержка до 124 ведомых устройств, конфигурирование с помощью Siemens SIMATIC Manager
Изделие: 342-2IA71
Для шины SPEED-Bus, ведущее устройство сети INTERBUS (2 канала RS-422), до 512 ведомых устройств, соединители Sub-D 9, диагностические порты (RJ45)
Изделие: 342-1CA70
Для шины SPEED-Bus, ведущее устройство сети CANopen, поддержка до 125 ведомых устройств, конфигурирование с помощью ПО VIPA WinCoCT
Изделие: 343-2AH10
Ведущее устройство AS-i, подключение до 62 ведомых устройств