Order no.
|
231-1BD40
|
Type |
SM 231, ECO |
General information
|
Note |
- |
Features |
4 inputs Configurable Current 4...20 mA, +/-20 mA |
Current consumption/power loss
|
Current consumption from backplane bus |
120 mA |
Power loss |
0.6 W |
Technical data analog inputs
|
Number of inputs |
4 |
Cable length, shielded |
200 m |
Rated load voltage |
- |
Current consumption from load voltage L+ (without load) |
- |
Voltage inputs |
- |
Min. input resistance (voltage range) |
- |
Input voltage ranges |
- |
Operational limit of voltage ranges |
- |
Operational limit of voltage ranges with SFU |
- |
Basic error limit voltage ranges |
- |
Basic error limit voltage ranges with SFU |
- |
Destruction limit current |
- |
Current inputs |
 |
Max. input resistance (current range) |
110 Ω |
Input current ranges |
-20 mA ... +20 mA +4 mA ... +20 mA |
Operational limit of current ranges |
+/-0.2% ... +/-0.5% |
Operational limit of current ranges with SFU |
- |
Radical error limit current ranges with SFU |
+/-0.1% ... +/-0.2% |
Radical error limit current ranges with SFU |
- |
Destruction limit current inputs (electrical current) |
- |
Destruction limit current inputs (voltage) |
- |
Resistance inputs |
- |
Resistance ranges |
- |
Operational limit of resistor ranges |
- |
Operational limit of resistor ranges with SFU |
- |
Basic error limit |
- |
Basic error limit with SFU |
- |
Destruction limit resistance inputs |
- |
Resistance thermometer inputs |
- |
Resistance thermometer ranges |
- |
Operational limit of resistance thermometer ranges |
- |
Operational limit of resistance thermometer ranges with SFU |
- |
Basic error limit thermoresistor ranges |
- |
Basic error limit thermoresistor ranges with SFU |
- |
Destruction limit resistance thermometer inputs |
- |
Thermocouple inputs |
- |
Thermocouple ranges |
- |
Operational limit of thermocouple ranges |
- |
Operational limit of thermocouple ranges with SFU |
- |
Basic error limit thermoelement ranges |
- |
Basic error limit thermoelement ranges with SFU |
- |
Destruction limit thermocouple inputs |
- |
Programmable temperature compensation |
- |
External temperature compensation |
- |
Internal temperature compensation |
- |
Internal temperature compensation |
- |
Technical unit of temperature measurement |
- |
Resolution in bit |
13 |
Measurement principle |
successive approximation |
Basic conversion time |
2 ms / channel |
Noise suppression for frequency |
f=50 Hz...400 Hz |
Initial data size |
8 Byte |
Status information, alarms, diagnostics
|
Status display |
none |
Interrupts |
no |
Process alarm |
no |
Diagnostic interrupt |
no |
Diagnostic functions |
no |
Diagnostics information read-out |
none |
Supply voltage display |
none |
Group error display |
red SF LED |
Channel error display |
none |
Isolation
|
Between channels |
- |
Between channels of groups to |
- |
Between channels and backplane bus |
 |
Between channels and power supply |
- |
Max. potential difference between circuits |
- |
Max. potential difference between inputs (Ucm) |
DC 2 V |
Max. potential difference between Mana and Mintern (Uiso) |
- |
Max. potential difference between inputs and Mana (Ucm) |
- |
Max. potential difference between inputs and Mintern (Uiso) |
DC 75 V/ AC 60 V |
Max. potential difference between Mintern and outputs |
- |
Insulation tested with |
DC 500 V |
Datasizes
|
Input bytes |
8 |
Output bytes |
0 |
Parameter bytes |
12 |
Diagnostic bytes |
0 |
Housing
|
Material |
PPE / PA 6.6 |
Mounting |
Profile rail 35 mm |
Mechanical data
|
Dimensions (WxHxD) |
25.4 mm x 76 mm x 88 mm |
Weight |
90 g |
Environmental conditions
|
Operating temperature |
0 °C to 60 °C |
Storage temperature |
-25 °C to 70 °C |
Certifications
|
UL508 certification |
yes |