Модуль аналогового ввода, 1 канал для подключения тензометрического датчика по 4- и 6-проводной схеме, разрешение 16 (24) разряда, авто и самокалибровка
Наименование
|
SM 031, 16 (24)Bit, 4- or 6-wire measurement |
Тип
|
031-1CA20 |
Габаритные размеры, В х Ш х Г, мм
|
12.9 mm x 109 mm x 76.5 mm |
Температура окружающей среды
|
0 °C ... 60 °C |
Количество входов
|
1 |
|
Status indication
RUN | MF | Description | |
green | red |
|
|
● | ○ | Bus communication is OK Module status is OK |
|
● | ● |
Bus communication is OK |
|
○ | ● |
Bus communication is not possible |
|
○ | ○ | Error at bus power supply | |
X | B |
Error in configuration |
|
on: ● | off: ○ | blinks with 2Hz: B | not relevant: X |
STEADY | CAL | FREECE | EXC | SENSE | DIFF | Description |
green | green | green | red | red | red |
|
● | X | X | X | X | X | On in Steady State. |
X | ● | X | X | X | X |
On at active self-calibration |
X | X | ● | X | X | X |
On at activated Input-Freeze. |
X | X | X | ● | X | X |
On at short circuit respectively |
X | X | X | X | ● | X |
On at overrange of the excitation voltage |
X | X | X | X | X | ● |
On at overrange of the differential voltage |
on: ● | off: ○ | blinks with 2Hz: B | not relevant: X |
Pin assignment
PM - Power module | Pos. | Function |
Type |
Description | |
1 | SIG+ | I |
+ Signal of the differential voltage USIG of the measuring bridge |
||
2 | SIG- | I |
- Signal of the differential voltage USIG of the measuring bridge |
||
3 | EXC- | O |
- Signal of the excitation voltage UEXC |
||
4 | Shield | --- | Connection for cable shield | ||
5 | SEN+ | I | + Sensor of the excitation voltage USEN | ||
6 | SEN- | I |
- Sensor of the excitation voltage USEN |
||
7 | EXC+ | O |
+ Signal of the excitation voltage UEXC |
||
8 | Shield | --- | Connection for cable shield |
O: Output, I: Input
Order no. |
031-1CA20 |
Type | SM 031 |
Module ID | 0841 1809 |
General information |
|
Note | - |
Features | Direct connection of a resistor full bridge (DMS) or load cell 4- or 6-wire connection 16 (24)Bit resolution Auto/self calibration zero point and final value Absolute exactness radical error ±0,1% (± 0,01%) Onboard power supply 2V5, 5V, 7V5, 10V und 12V |
Technical data strain gauge DMS |
|
Number of inputs | 1 |
Cable length, shielded | 200m |
Rated load voltage | DC 24 V |
Reverse polarity protection of rated load voltage | |
Current consumption from load voltage L+ (without load) | 85mA |
Relative accuracy according to self-calibration | +/-0.01% |
Operational limit Usense | +/-0.2% |
Operational limit Usig | +/-0.2% |
Basic error limit Usense | +/-0.1% |
Basic error limit Usig | +/-0.1% |
Destruction limit current | max. 12V |
External bridge supply possible | - |
Configurable bridge supply | 2.5V / max. 120mA-5V / max. 120mA-7.5V / max. 100mA-10V / max. 90mA-12V / max. 80mA |
Resolution in bit | 24 |
Measurement principle | successive approximation |
Basic conversion time | 1ms cycle, 10ms...330ms depending on the filter |
Input filter Hardware | Low pass 10kHz 3rd order |
Input filter software | Dynamic IIR filter-configurable IIR filter 0.1Hz...1000Hz-configurable FIR filter 50Hz/60Hz |
Initial data size | 4Byte |
Data for selection of the strain gauge DMS sensor |
|
Bridge supply voltage EXC | 0...12V |
Bridge differential voltage SIG | +/-29mV |
Rated output | 0.5...4mV/V |
4 wire connection possible | |
6 wire connection possible | |
possible bridge configuration | symmetric full bridge |
Housing |
|
Material | PC / PPE GF10 |
Mounting | Profile rail 35 mm |
Mechanical data |
|
Dimensions (WxHxD) | 12.9mm x 109mm x 76.5mm |
Weight | 60g |
Environmental conditions |
|
Operating temperature | 0 °C to 60 °C |
Storage temperature | -25 °C to 70 °C |
Certifications |
|
UL508 certification | in preparation |
Order no. | Name/Description | |
---|---|---|
031-1BB10 |
SM 031 - Analog input 2 inputs 12Bit Current 0(4)...20mA 2 wire |
[Datasheet] [Manual] [STP] |
031-1BB30 |
SM 031 - Analog input 2 inputs 12Bit Voltage 0...10 V |
[Datasheet] [Manual] [STP] |
031-1BB40 |
SM 031 - Analog input 2 inputs 12Bit Current 0(4)...20 mA |
[Datasheet] [Manual] [STP] |
031-1BB60 |
SM 031 - Analog input 2 inputs 12Bit Current 0(4)...20mA 2 wire |
[Datasheet] [Manual] [STP] |
031-1BB70 |
SM 031 - Analog input 2 inputs 12Bit Voltage -10 V...+10 V |
[Datasheet] [Manual] [STP] |
031-1BB90 |
SM 031 - Analog input 2 inputs 16Bit Thermocouple type J, K, N, R, S, T, B, C, E, L Voltage -80mV...+80mV |
[Datasheet] [Manual] [STP] |
031-1BD30 |
SM 031 - Analog input 4 inputs 12Bit Voltage 0...10 V |
[Datasheet] [Manual] [STP] |
031-1BD40 |
SM 031 - Analog input 4 inputs 12Bit Current 0(4)...20 mA |
[Datasheet] [Manual] [STP] |
031-1BD70 |
SM 031 - Analog input 4 inputs 12Bit Voltage -10 V...+10 V |
[Datasheet] [Manual] [STP] |
031-1BD80 |
SM 031 - Analog input 4 inputs 16Bit 0 .. 3000 ohm resistance Resistance measurement with 2, 3, and 4-wires |
[Datasheet] [Manual] [STP] |
031-1BF60 |
SM 031 - Analog input 8 inputs 12Bit Current 0(4)...20mA 2 wire |
[Datasheet] [Manual] |
031-1BF74 |
SM 031 - Analog input 8 inputs 12Bit Voltage -10 V...+10 V |
[Datasheet] [Manual] |
031-1CA20 |
SM 031 - Analog input Direct connection of a resistor full bridge (DMS) or load cell 4- or 6-wire measurement 16 (24)Bit resolution Auto/self calibration zero point and final value Absolute exactness radical error ±0,1% (± 0,01%) Onboard power supply 2V5, 5V, 7V5, 10V and 12V |
[Datasheet] [Shortfacts] [Manual] |
031-1CB30 |
SM 031 - Analog input 2 inputs 16Bit Voltage 0...10 V |
[Datasheet] [Manual] [STP] |
031-1CB40 |
SM 031 - Analog input 2 inputs 16Bit Current 0(4)...20 mA |
[Datasheet] [Manual] [STP] |
031-1CB70 |
SM 031 - Analog input 2 inputs 16Bit Voltage -10 V...+10 V |
[Datasheet] [Manual] [STP] |
031-1CD30 |
SM 031 - Analog input 4 inputs 16Bit Voltage 0...10 V |
[Datasheet] [Manual] [STP] |
031-1CD35 |
SM 031 - Analog input 4 inputs 16Bit Voltage 0...10 V |
[Datasheet] [Manual] [STP] |
031-1CD40 |
SM 031 - Analog input 4 inputs 16Bit Current 0(4)...20 mA |
[Datasheet] [Manual] [STP] |
031-1CD45 |
SM 031 - Analog input 4 inputs 16Bit Current 0(4)...20 mA |
[Datasheet] [Manual] [STP] |
031-1CD70 |
SM 031 - Analog input 4 inputs 16Bit Voltage -10 V...+10 V |
[Datasheet] [Manual] [STP] |
031-1LB90 |
SM 031 - Analog input 2 inputs 16Bit Thermocouple Voltage -80mV...+80mV requires less parameter bytes than module 031-1BB90 |
[Datasheet] [Manual] [STP] |
031-1LD80 |
SM 031 - Analog input 4 inputs 16Bit 0 .. 3000 ohm resistance Resistance measurement with 2, 3, and 4-wires requires less parameter bytes than module 031-1BD80 |
[Datasheet] [Manual] [STP] |
032-1BB30 |
SM 032 - Analog output 2 outputs 12Bit Voltage 0...10 V |
[Datasheet] [Manual] [STP] |
032-1BB40 |
SM 032 - Analog output 2 outputs 12Bit Current 0(4)...20 mA |
[Datasheet] [Manual] [STP] |
032-1BB70 |
SM 032 - Analog output 2 outputs 12Bit Voltage -10 V...+10 V |
[Datasheet] [Manual] [STP] |
032-1BD30 |
SM 032 - Analog output 4 outputs 12Bit Voltage 0...10 V |
[Datasheet] [Manual] [STP] |
032-1BD40 |
SM 032 - Analog output 4 outputs 12Bit Current 0(4)...20mA |
[Datasheet] [Manual] [STP] |
032-1BD70 |
SM 032 - Analog output 4 outputs 12Bit Voltage -10 V...+10 V |
[Datasheet] [Manual] [STP] |
032-1CB30 |
SM 032 - Analog output 2 outputs 16Bit Voltage 0...10 V |
[Datasheet] [Manual] [STP] |
032-1CB40 |
SM 032 - Analog output 2 outputs 16Bit Current 0(4)...20 mA |
[Datasheet] [Manual] |
032-1CB70 |
SM 032 - Analog output 2 outputs 16Bit Voltage -10 V...+10 V |
[Datasheet] [Manual] [STP] |
032-1CD30 |
SM 032 - Analog output 4 outputs 16Bit Voltage 0...10 V |
[Datasheet] [Manual] [STP] |
032-1CD40 |
SM 032 - Analog output 4 outputs 16Bit Current 0(4)...20mA |
[Datasheet] [Manual] |
032-1CD70 |
SM 032 - Analog output 4 outputs 16Bit Voltage -10 V...+10 V |
[Datasheet] [Manual] [STP] |
031-1PA00 |
Energy measurement terminal 1/3 phase 230/400V 1A Resolution measured value |
[Datasheet] [Manual] |
Изделие: 031-1BB10
2 изолированных канала, 12 разрядов, входной диапазон 0/4–20 мА
Изделие: 031-1BB70
2 канала, 12 разрядов, входной диапазон ±10 В
Изделие: 031-1LD80
4 канала, 16 разрядов, работа с резисторами и термометрами сопротивления
Изделие: 031-1BB60
2 канала, 12 разрядов, входной диапазон 0/4–20 мА, 2-проводная схема