Модуль дискретного ввода, 8 каналов 24 В пост. тока, контроль целостности сигнальных цепей
Наименование
|
Модуль дискретных входов SM 021, DI 8xDC 24V, diagnosis of wiring errors |
Тип
|
021-1DF00 |
Габаритные размеры, В х Ш х Г, мм
|
12.9 mm x 109 mm x 76.5 mm |
Температура окружающей среды
|
0 °C .. 60 °C |
Количество входов
|
8 |
Тип входного сигнала
|
24VDC |
|
Status indication
RUN | MF | DI x | Description | |
green | red | green |
|
|
● | ○ | X | Bus communication is OK Module status is OK |
|
● | ● | X |
Bus communication is OK |
|
○ | ● | X |
Bus communication is not possible |
|
○ | ○ | X | Error at bus power supply | |
X | B | X |
Error in configuration |
|
● | ○ | ● | Digital input has signal "1" | |
● | ○ | ○ | Digital input has signal "0" | |
on: ● | off: ○ | blinks with 2Hz: B | not relevant: X |
Pin assignment
PM - Power module | Pos. | Function |
Type |
Description | |
1 | DI 0 | I | Digital input DI 0 | ||
2 | DI 2 | I |
Digital input DI 2 |
||
3 | DI 4 | I |
Digital input DI 4 |
||
4 | DI 6 | I | Digital input DI 6 | ||
5 | DI 1 | I | Digital input DI 1 | ||
6 | DI 3 | I |
Digital input DI 3 |
||
7 | DI 5 | I |
Digital input DI 5 |
||
8 | DI 7 | I | Digital input DI 7 |
I: Input
Order no. |
021-1DF00 |
Type | SM 021 |
Module ID | 0012 1F41 |
General information |
|
Note | - |
Features | 8 inputs diagnosis of wiring errors |
Current consumption/power loss |
|
Current consumption from backplane bus | 60 mA |
Power loss | 1.1 W |
Technical data digital inputs |
|
Number of inputs | 8 |
Cable length, shielded | 1000 m |
Cable length, unshielded | 600 m |
Rated load voltage | - |
Current consumption from load voltage L+ (without load) | - |
Rated value | DC 20.4...28.8 V |
Input voltage for signal "0" | DC 0...5 V |
Input voltage for signal "1" | DC 10,8...28,8 V |
Input voltage hysteresis | - |
Frequency range | - |
Input resistance | - |
Input current for signal "1" | 3 mA |
Connection of Two-Wire-BEROs possible | |
Max. permissible BERO quiescent current | 1.5 mA |
Input delay of "0" to "1" | parameterizable 100µs - 20ms |
Input delay of "1" to "0" | parameterizable 100µs - 20ms |
Number of simultaneously utilizable inputs horizontal configuration | 8 |
Number of simultaneously utilizable inputs vertical configuration | 8 |
Input characteristic curve | IEC 61131-2, type 3 |
Initial data size | 8 Bit |
Status information, alarms, diagnostics |
|
Status display | green LED per channel |
Interrupts | yes |
Process alarm | no |
Diagnostic interrupt | yes, parameterizable |
Diagnostic functions | yes |
Diagnostics information read-out | possible |
Module state | green LED |
Module error display | red LED |
Channel error display | none |
Isolation |
|
Between channels | - |
Between channels of groups to | - |
Between channels and backplane bus | |
Insulation tested with | DC 500 V |
Safety |
|
Safety protocol | - |
Safety requirements | - |
Secure user address | - |
Watchdog | - |
Two channels | - |
Test pulse outputs | - |
Datasizes |
|
Input bytes | 1 |
Output bytes | 0 |
Parameter bytes | 12 |
Diagnostic bytes | 20 |
Housing |
|
Material | PPE / PPE GF10 |
Mounting | Profile rail 35 mm |
Mechanical data |
|
Dimensions (WxHxD) | 12.9 mm x 109 mm x 76.5 mm |
Weight | 60 g |
Environmental conditions |
|
Operating temperature | 0 °C to 60 °C |
Storage temperature | -25 °C to 70 °C |
Certifications |
|
UL certification | in preparation |
KC certification | yes |
Order no. | Name/Description | |
---|---|---|
021-1BB00 |
SM 021 - Digital input 2 inputs |
[Datasheet] [Manual] [STP] |
021-1BB10 |
SM 021 - Digital input 2 fast inputs Input filter time delay parameterizable 2 µs...4 ms |
[Datasheet] [Manual] [STP] |
021-1BB50 |
SM 021 - Digital input 2 inputs Active low input |
[Datasheet] [Manual] [STP] |
021-1BB70 |
SM 021 - Digital input 2 inputs Time stamp |
[Datasheet] [Manual] [STP] |
021-1BD00 |
SM 021 - Digital input 4 inputs |
[Datasheet] [Manual] [STP] |
021-1BD10 |
SM 021 - Digital input 4 fast inputs Input filter time delay parameterizable 2 µs...4 ms |
[Datasheet] [Manual] [STP] |
021-1BD40 |
SM 021 - Digital input 4 inputs Connect 2/3-wire |
[Datasheet] [Manual] [STP] |
021-1BD50 |
SM 021 - Digital input 4 inputs Active low input |
[Datasheet] [Manual] [STP] |
021-1BD70 |
SM 021 - Digital input 4 inputs Time stamp |
[Datasheet] [Manual] [STP] |
021-1BF00 |
SM 021 - Digital input 8 inputs |
[Datasheet] [Manual] [STP] |
021-1BF01 |
SM 021 - Digital input 8 Inputs, 0.5ms |
[Datasheet] [Manual] |
021-1BF50 |
SM 021 - Digital input 8 inputs Active low input |
[Datasheet] [Manual] [STP] |
021-1DF00 |
SM 021 - Digital input 8 inputs diagnosis of wiring errors |
[Datasheet] [Manual] [STP] |
021-1SD00 |
SM 021 - Digital input 4 inputs Safety |
[Datasheet] [Manual] [Manual] [STP] |
022-1BB00 |
SM 022 - Digital output 2 outputs Output current 0.5 A |
[Datasheet] [Manual] [STP] |
022-1BB20 |
SM 022 - Digital output 2 outputs Output current 2 A |
[Datasheet] [Manual] [STP] |
022-1BB50 |
SM 022 - Digital output 2 Low-Side outputs Output current 0.5 A |
[Datasheet] [Manual] [STP] |
022-1BB70 |
SM 022 - Digital output 2 outputs Time stamp Output current 0.5 A |
[Datasheet] [Manual] [STP] |
022-1BB90 |
SM 022 - Digital output 2 outputs PWM |
[Datasheet] [Manual] [STP] |
022-1BD00 |
SM 022 - Digital output 4 outputs Output current 0.5 A |
[Datasheet] [Manual] [STP] |
022-1BD20 |
SM 022 - Digital output 4 outputs Output current 2 A |
[Datasheet] [Manual] [STP] |
022-1BD50 |
SM 022 - Digital output 4 Low-Side outputs Output current 0.5 A |
[Datasheet] [Manual] [STP] |
022-1BD70 |
SM 022 - Digital output 4 outputs Time stamp Output current 0.5 A |
[Datasheet] [Manual] [STP] |
022-1BF00 |
SM 022 - Digital output 8 outputs Output current 0.5 A |
[Datasheet] [Manual] [STP] |
022-1BF50 |
SM 022 - Digital output 8 Low-Side outputs Output current 0.5 A |
[Datasheet] [Manual] [STP] |
022-1DF00 |
SM 022 - Digital output 8 outputs Output current 0.5 A diagnosis of wiríng errors |
[Datasheet] [Manual] [STP] |
022-1HB10 |
SM 022 - Digital output 2 relay outputs DC 30 V/ AC 230 V Output current 3 A |
[Datasheet] [Manual] [STP] |
022-1SD00 |
SM 022 - Digital output 4 outputs Safety Output current 0.5 A |
[Datasheet] [Manual] [Manual] [STP] |
Изделие: 021-1BD10
4 канала 24 В пост. тока, время задержки входного фильтра 2 мкс...3 мс
Изделие: 021-1BD40
4 канала 24 В пост. тока, 2/3-проводная схема подключения